AWX NH3-3 200
Standard 3-Series
- Nominal Range 0 – 100 ppm
- Maximum Overload 200 ppm
- Expected Operation Life 2 years in air
- Output Signal 100 +/- 20 nA/ppm
- Resolution 1.0 ppm
- Temperature Range - 10 °C to + 40 °C
- Pressure Range Atmospheric +/-10 %
- t90 Response Time < 50 sec
- Relative Humidity Range 15 % to 90 % R.H. non-condensing
- Typical Baseline Range (pure air, 20°C) – +/- 7 ppm
- Maximum Zero Shift (+20°C to +40 °C) -7.0 ppm
- Expected Long Term Output Drift < 1 % signal loss/month
- Recommended Load Resistor 10 Ohm
- Bias Voltage Not required
- Repeatability < 2 % of signal
- Output Linearity Linear
-
AWX NH3-4 100
Mini 4-Series
- Nominal Range 0 – 100 ppm
- Maximum Overload 200 ppm
- Expected Operation Life 2 years in air
- Output Signal 100 +/- 20 nA/ppm
- Resolution 1 ppm
- Temperature Range - 10 °C to + 50 °C
- Pressure Range Atmospheric +/-10 %
- t90 Response Time < 30 sec
- Relative Humidity Range 15 % to 90 % R.H. non-condensing
- Typical Baseline Range (pure air, 20°C) 0 ppm to +/-4 ppm
- Maximum Zero Shift (+20°C to +40 °C) -8 ppm
- Expected Long Term Output Drift < 5 % signal loss/6 month
- Recommended Load Resistor 10 Ohm
- Bias Voltage Not required
- Repeatability < 3 % of signal
- Output Linearity Linear
-
AWX NH3-7 200
Compact 7-Series
- Nominal Range 0 – 100 ppm
- Maximum Overload 200 ppm
- Expected Operation Life 2 years in air
- Output Signal 100 +/- 20 nA/ppm
- Resolution 1.0 ppm
- Temperature Range - 10 °C to + 40 °C
- Pressure Range Atmospheric +/-10 %
- t90 Response Time < 50 sec
- Relative Humidity Range 15 % to 90 % R.H. non-condensing
- Typical Baseline Range (pure air, 20°C) – +/- 7 ppm
- Maximum Zero Shift (+20°C to +40 °C) -7.0 ppm
- Expected Long Term Output Drift < 1 % signal loss/month
- Recommended Load Resistor 10 Ohm
- Bias Voltage Not required
- Repeatability < 2 % of signal
- Output Linearity Linear